Abstract

Anti-islanding protection is one of the main protection requirements for Distributed Generation (DG). Grid tied DG systems are equipped with an islanding detection method that is responsible for detecting the loss of mains in a timely manner in order to initiate DG disconnection. Frequency relays are commonly used in detecting an islanding condition for synchronous based Distributed Generation (DG). The effectiveness of frequency relays are assessed using performance curves which provide a relationship between the islanding detection time and the amount of active power mismatch. This paper examines the impact of operating multiple synchronous based DG units on the islanding detection capability and performance curves of frequency relays. The results show that, with multiple synchronous DG units, the performance curve of frequency relays will be altered depending on the equivalent inertia constant of the islanded DG system.

Original languageBritish English
Title of host publicationProceedings - 2012 IEEE International Symposium on Industrial Electronics, ISIE 2012
Pages1616-1620
Number of pages5
DOIs
StatePublished - 2012
Event21st IEEE International Symposium on Industrial Electronics, ISIE 2012 - Hangzhou, China
Duration: 28 May 201231 May 2012

Publication series

NameIEEE International Symposium on Industrial Electronics

Conference

Conference21st IEEE International Symposium on Industrial Electronics, ISIE 2012
Country/TerritoryChina
CityHangzhou
Period28/05/1231/05/12

Fingerprint

Dive into the research topics of 'Performance of frequency relays with multiple synchronous based DG units'. Together they form a unique fingerprint.

Cite this