Abstract
Wind farms (WFs) are increasingly integrated with high-voltage (HV) grids, for which distance relaying is normally the protection of choice. This paper reveals some serious defects of distance protection for the lines connected to induction generator (IG)-based WFs during balanced faults. It is shown that for the squirrel cage IG (SCIG) WFs, distance protection becomes insecure, while for the doubly fed IG (DFIG) WFs, the relay performance is utterly unreliable, due to operating scenarios that are unique to such WFs, and are unfamiliar to the existing relaying practices. The detected failures can easily result in unnecessary WF tripping, thus jeopardizing the objectives pursued by the new grid codes that oblige WFs to remain connected to the grid during disturbances. Moreover, a novel modified permissive overreach transfer trip (POTT) scheme along with a fault current classification technique is proposed to address these problems for both types of IG-based WFs, and the accurate nondelayed protection of a distance relay over the entire line length is restored. A comprehensive performance evaluation confirms the findings of this paper and validates the efficacy of the proposed solution for all operating conditions. Results are particularly promising for the DFIG-based WFs with nonzero crowbar resistance, which is the most likely situation confronted by distance relays.
| Original language | British English |
|---|---|
| Article number | 6877744 |
| Pages (from-to) | 1193-1203 |
| Number of pages | 11 |
| Journal | IEEE Transactions on Sustainable Energy |
| Volume | 5 |
| Issue number | 4 |
| DOIs | |
| State | Published - 1 Oct 2014 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Distance relay
- doubly fed induction generator (IG)
- squirrel cage induction generator (SCIG)
- wind farm (WF)
Fingerprint
Dive into the research topics of 'Distance protection of lines connected to induction generator-based wind farms during balanced faults'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver