TY - JOUR
T1 - An Auxiliary Framework to Mitigate Measurement Inaccuracies Caused by Capacitive Voltage Transformers
AU - Ameli, Amir
AU - Ghafouri, Mohsen
AU - Salama, Magdy M.A.
AU - El-Saadany, Ehab F.
N1 - Funding Information:
This work was supported in part by Khalifa University, Abu Dhabi, United Arab Emirates, under Grant CIRA-013-2020; in part by the Natural Sciences and Engineering Research Council of Canada (NSERC) under Grant RGPIN-2021-04042; and in part by the Fonds de recherche du Quebec-Nature et technologies (FRQNT) under Grant 2022-NC-300985.
Publisher Copyright:
© 1963-2012 IEEE.
PY - 2022
Y1 - 2022
N2 - The substantial cost of voltage transformers in high- and extra-high-voltage levels has persuaded power engineers to widely utilize capacitive voltage transformers (CVTs) in transmission systems. CVTs, however, demonstrate an inferior transient response in certain situations, which distorts their secondary voltages. Consequently, the voltage waveform produced by a CVT might not be an accurate stepped-down version of its primary voltage and can result in malfunction of power system components, such as overreaching of distance relays. This article proposes an auxiliary voltage-compensation-based framework to mitigate measurement inaccuracies caused by the weak transient response of CVTs. This framework enables power system components, such as relays, to work accurately when the secondary voltage of CVTs is distorted, without sacrificing their sensitivity and/or operation speed. The proposed method models a CVT with its state-space representation and uses unknown input observers to estimate the states of the CVT and its primary voltage, which is modeled as an unknown input. Thus, after implementing the proposed auxiliary framework, the estimated primary voltage of CVTs is used, instead of their distorted secondary voltages, in power system applications. The results of electromagnetic transient simulation in MATLAB/Simulink corroborate the effectiveness of the proposed method under various conditions and prove its independence from system and fault parameters.
AB - The substantial cost of voltage transformers in high- and extra-high-voltage levels has persuaded power engineers to widely utilize capacitive voltage transformers (CVTs) in transmission systems. CVTs, however, demonstrate an inferior transient response in certain situations, which distorts their secondary voltages. Consequently, the voltage waveform produced by a CVT might not be an accurate stepped-down version of its primary voltage and can result in malfunction of power system components, such as overreaching of distance relays. This article proposes an auxiliary voltage-compensation-based framework to mitigate measurement inaccuracies caused by the weak transient response of CVTs. This framework enables power system components, such as relays, to work accurately when the secondary voltage of CVTs is distorted, without sacrificing their sensitivity and/or operation speed. The proposed method models a CVT with its state-space representation and uses unknown input observers to estimate the states of the CVT and its primary voltage, which is modeled as an unknown input. Thus, after implementing the proposed auxiliary framework, the estimated primary voltage of CVTs is used, instead of their distorted secondary voltages, in power system applications. The results of electromagnetic transient simulation in MATLAB/Simulink corroborate the effectiveness of the proposed method under various conditions and prove its independence from system and fault parameters.
KW - Capacitive voltage transformers (CVTs)
KW - distance relays
KW - measurement inaccuracies
KW - overreach
KW - state estimation
KW - unknown input observers (UIOs)
UR - http://www.scopus.com/inward/record.url?scp=85122864178&partnerID=8YFLogxK
U2 - 10.1109/TIM.2022.3142040
DO - 10.1109/TIM.2022.3142040
M3 - Article
AN - SCOPUS:85122864178
SN - 0018-9456
VL - 71
JO - IEEE Transactions on Instrumentation and Measurement
JF - IEEE Transactions on Instrumentation and Measurement