T1 - A signed correlation index-based differential protection scheme for inverter-based islanded microgrids
AU - Saber, A.
AU - Zeineldin, H. H.
AU - EL-Fouly, Tarek H.M.
AU - Al-Durra, Ahmed
N1 - Funding Information:
This work was supported by the Khalifa University of Science and Technology under Award No. CIRA- 2019-049.
Publisher Copyright:
© 2022 Elsevier Ltd
PY - 2023/2
Y1 - 2023/2
N2 - The different fault characteristics of the inverter-based distributed generation (IBDG) units make the protection of the inverter-based islanded microgrids (IBIMGs) a formidable task. According to IEEE Std 1547.4, the limited fault current levels associated with the IBIMGs may result in misleading decisions of the traditional protective relays during fault occurrence. In this paper, a new differential protection scheme for the IBIMGs is introduced based on the signed correlation technique. The proposed scheme is formulated based on the signs of the instantaneous phase currents at both line ends instead of the current magnitudes. In addition, a signed correlation index is defined to measure the similarity between the signs of the instantaneous phase currents at both line ends employing only a time window of half-cycle. Moreover, a fault detection index is introduced to discriminate the internal faults from other events. In order to validate the proposed scheme, the 9-bus IBIMG and the modified IEEE 33-bus system are simulated on the PSCAD/EMTDC platform, and several scenarios are conducted, including load switching, outage of IBDG units, external bus faults, and internal faults. The obtained results emphasize that the proposed scheme operates correctly considering all types of faults, different fault resistances and inception angles, as well as measurement and synchronization errors.
AB - The different fault characteristics of the inverter-based distributed generation (IBDG) units make the protection of the inverter-based islanded microgrids (IBIMGs) a formidable task. According to IEEE Std 1547.4, the limited fault current levels associated with the IBIMGs may result in misleading decisions of the traditional protective relays during fault occurrence. In this paper, a new differential protection scheme for the IBIMGs is introduced based on the signed correlation technique. The proposed scheme is formulated based on the signs of the instantaneous phase currents at both line ends instead of the current magnitudes. In addition, a signed correlation index is defined to measure the similarity between the signs of the instantaneous phase currents at both line ends employing only a time window of half-cycle. Moreover, a fault detection index is introduced to discriminate the internal faults from other events. In order to validate the proposed scheme, the 9-bus IBIMG and the modified IEEE 33-bus system are simulated on the PSCAD/EMTDC platform, and several scenarios are conducted, including load switching, outage of IBDG units, external bus faults, and internal faults. The obtained results emphasize that the proposed scheme operates correctly considering all types of faults, different fault resistances and inception angles, as well as measurement and synchronization errors.
KW - Differential protection
KW - Fault Detection Index (FDI)
KW - Inverter-Based Islanded Microgrid (IBIMG)
KW - Signed Correlation Index (SCI)
UR - https://www.scopus.com/pages/publications/85140343896
U2 - 10.1016/j.ijepes.2022.108721
DO - 10.1016/j.ijepes.2022.108721
M3 - Article
AN - SCOPUS:85140343896
SN - 0142-0615
VL - 145
JO - International Journal of Electrical Power and Energy Systems
JF - International Journal of Electrical Power and Energy Systems
M1 - 108721
ER -